CHECKSHEET CUM LOG BOOK FOR PERIODIC OVERHAULING (POH) OF RMPU AND CONTROL PANEL OF AIR-CONDITIONING COACHES | ||||||||||||
COACH NO. | CODE : | RLY.: | Work starting date : | |||||||||
PP SIDE/MAKE : | Sr. No. | Work completion date : | ||||||||||
NPP SIDE/MAKE: | Sr. No. | Total time taken: | ||||||||||
DATE : | ||||||||||||
Sr. | JOB DESCRIPTION | SPECIFIED VALUE | ACTUAL VALUE | REMARKS | ||||||||
PP | NPP | PP | NPP | |||||||||
1 | Removing of dust and dirt from control panel & condenser coil, cooling coil. | Should be cleaned. | Should be cleaned. | |||||||||
2 | Replacement of filter | RETURN AIR | 100% New | 100% New | ||||||||
FRESH AIR | 100% New | 100% New | ||||||||||
3 | Replacement of condenser & blower motor. | 100% POH | 100% POH | |||||||||
4 | Replacement of condenser fan blade. | Stainless steel to new FRP | Stainless steel to new FRP | Replacement of FRP blades on conditional basis and replace SS blades with new FRP blades. | ||||||||
5 | Checking of Electronic thermostat | L | H | L | H | L | H | L | H | Replace Electronic thermostat by new on conditional basis | ||
Cooling | 230C | 250C | 230C | 250C | ||||||||
Heating | 190C | 210C | 190C | 210C | ||||||||
6 | Normal current when package unit is in cooling mode. | 20-23 Amps | 20-23 Amps | |||||||||
7 | Normal current when package unit is in heating mode. | 07-11 Amps | 07-11 Amps | |||||||||
8 | Compressor-1 (CP 1) Current. | 07-10 Amps | 07-10 Amps | |||||||||
Compressor-2 (CP 2) Current. | 07-10 Amps | 07-10 Amps | ||||||||||
9 | Condenser motor-1 (CD 1) Current. | 1.5-2.1 Amps | 1.5-2.1 Amps | |||||||||
Condenser motor-2 (CD 2) Current. | 1.5-2.1 Amps | 1.5-2.1 Amps | ||||||||||
10 | Blower motor Current. | 1.5-2.5 Amps | 1.5-2.5 Amps | |||||||||
11 | Over heat protection with fixed setting at 650C | OHP-1 & OHP-II | (Fixed Setting 650C) Trip within 5 min. | (Fixed Setting 650C) Trip within 5 min. | Replacement on conditional basis. | |||||||
12 | HP cut out- (Range 85 to 425 PSI) | HP-I | 415 PSI (Trip within 10 min. with condenser motor OFF). | 415 PSI (Trip within 10 min. with condenser motor OFF). | ||||||||
HP - II | ||||||||||||
13 | LP cut out- (Range 15 to 100 PSI) | LP-I | 35 PSI | 35 PSI | ||||||||
LP - II | ||||||||||||
14 | Functional check of Timers- (Range 00 to 180 Sec.) | TDR1 | 2.0 min | 2.0 min | Replacement on conditional basis. | |||||||
TDR2 | 2.5 min | 2.5 min | ||||||||||
15 | Functional check of OLR of Compressor (Range 7.5 to 11Amps) | CP 1 | (10 Amp setting) | (10 Amp setting) | Replacement on conditional basis. | |||||||
CP 2 | (10 Amp setting) | (10 Amp setting) | ||||||||||
Functional check of OLR of condensor motor (Range 1.7 to 2.4 Amps) | CD 1 | (2.1 Amp setting) | (2.1 Amp setting) | |||||||||
CD 2 | (2.1 Amp setting) | (2.1 Amp setting) | ||||||||||
Functional check of OLR of blower motor (Range 2.2 to 3.1 Amps) | Blower | (2.5 Amp setting) | (2.5 Amp setting) | |||||||||
16 | Functional check of contactor for Compressor (Range 32 Amps) | CP 1 | Conditional | Conditional | Replacement on conditional basis. | |||||||
CP 2 | Conditional | Conditional | ||||||||||
Functional check of contactor for condensor motor (Range 16 Amps) | CD 1 | Conditional | Conditional | |||||||||
CD 2 | Conditional | Conditional | ||||||||||
Functional check of contactor for blower motor (Range 16 Amps) | Blower | Conditional | Conditional | |||||||||
17 | Checking of Indication PCBs. | Working | Working | Replacement on conditional basis. | ||||||||
18 | Checking of MCBs. | Working | Working | Replacement on conditional basis. | ||||||||
19 | Checking of indication lamp. (R. Y. B.) | Working | Working | Replacement on conditional basis. | ||||||||
20 | Checking of all Electric conections. | Should be tight | Should be tight | |||||||||
21 | Functional check of Rotary switch (63 Amps. ON/OFF, 4 position) | RSW 1 | Working properly | Working properly | Replace rotary switches on conditional basis | |||||||
Functional check of Rotary switch (12 Amps.2 pole , 3-way with OFF.) | RSW 2 | Working properly | Working properly | |||||||||
Functional check of Rotary switch(16 Amps.3 pole , 4 position). (auto manual) | RSW 3 | Working properly | Working properly | |||||||||
Functional check of Rotary switch (10 Amps.2 pole , 3way without OFF.) | RSW 4 | Working properly | Working properly | |||||||||
22 | Ensure refrigerant pipes are clamped properly. | Properly clamped. | Properly clamped. | |||||||||
23 | Ensure suction pipe for proper lagging. | Properly lagged. | Properly lagged. | |||||||||
24 | Checking of vane relay. | By stopping the return air flow, AC plant & heater circuit should be cut OFF. | Replace vane relay on conditional basis | |||||||||
25 | Start the plant and check all the motors for abnormality. | Working properly | Working properly | |||||||||
26 | Check drip tray drain. | Should be Clean | Should be Clean | |||||||||
27 | Compressor terminal, wires and Thimbal connections. | Properly Tightened | Properly Tightened | |||||||||
28 | Antivibration mountings for RMPU. | Should be in good condition | Should be in good condition | Replacement on conditional basis. | ||||||||
29 | Heating elements (3 KW X 2). | Workinng properly | Workinng properly | Replacement on conditional basis. | ||||||||
30 | Unit and coach rubber lining. | 100% New | 100% New | |||||||||
31 | Rubber bushing/packing of pipe. | 100% New | 100% New | |||||||||
32 | Rubber gasket of Access door for fresh air filter & blower section. | 100% New | 100% New | |||||||||
33 | Condensing area covers, upper mesh guard, compressor side hinges and fastners. | Properly Tightened | Properly Tightened | |||||||||
34 | Earthing shunt with studs. | Properly Tightened | Properly Tightened | Replacement on conditional basis. | ||||||||
35 | All wires of unit, panel and between panel & unit. | Properly Tightened | Properly Tightened | |||||||||
36 | Checking of conduit pipes. | Properly fitted. | Properly fitted. | |||||||||
37 | Rubber canopy for condenser motor. (Water deflector) | Should be in good condition | Should be in good condition | Replacement on conditional basis. | ||||||||
38 | Check the supply of control transformer. | Working properly | Working properly | Replacement on conditional basis. | ||||||||
39 | Check the healthiness of Harness coupler. | Working properly | Working properly | Replacement on conditional basis. | ||||||||
40 | Mesh between Evaporator & heater. | Should be cleaned. | Should be cleaned. | Replacement on conditional basis. | ||||||||
41 | Base insulator for heating element. | Properly fitted. | Properly fitted. | Replacement on conditional basis. | ||||||||
42 | Knobs for Rotary switches. | Properly fitted. | Properly fitted. | Replacement on conditional basis. | ||||||||
43 | Canvas duct for supply & return air | 100%New | 100%New | |||||||||
44 | Running Gas pressure | Should be 60-65 PSI | Should be 60-65 PSI | CP-1 | CP-2 | CP-1 | CP-2 | |||||
MEGGER READING (In Mega Ohms) | ||||||||||||
Check insulation resistance of all motors and compressors by duly calibrated 500V megger. Insulation resistance of motors should not be less than 2 Mega Ohms. | Equipement | BLR | CD-1 | CD-2 | CP-1 | CP-2 | CCH | HTR | HP-1 | |||
PP-Side | ||||||||||||
NPP-Side | ||||||||||||
Equipement | LP-1 | HP-2 | LP-2 | OHP-1 | OHP-2 | VR | SENSOR | |||||
PP-Side | ||||||||||||
NPP-Side | ||||||||||||
Items not compliled: | ||||||||||||
Non-compliance pertmitted by: | ||||||||||||
NAME & SIGNATURE OF | NAME & SIGNATURE Of | |||||||||||
NOMINATED RAILWAY REPRESENTATIVE | FIRM REPRESENTATIVE | |||||||||||
FOR INSPECTION AT WORKSHOP |